【美国保险商实验室标准UL】UL 1626A outline of investigation for fire testing of residential sprinkle.doc
《【美国保险商实验室标准UL】UL 1626A outline of investigation for fire testing of residential sprinkle.doc》由会员分享,可在线阅读,更多相关《【美国保险商实验室标准UL】UL 1626A outline of investigation for fire testing of residential sprinkle.doc(20页珍藏版)》请在三一办公上搜索。
1、May 22, 20071SUBJECT 1626A OUTLINE OF INVESTIGATIONFORFIRE TESTING OF RESIDENTIAL SPRINKLERS FOR USE WITH SMOOTH, FLAT, SLOPED CEILINGS HAVING PITCHES NOT EXCEEDING 8/12Issue Number: 1May 22, 2007Summary of TopicsThis is the First Issue of the Subject 1626A Outline of Investigation for Fire Testing
2、of Residential Sprinklers for Use With Smooth, Flat, Sloped Ceilings Having Pitches not Exceeding 8/12.The UL Foreword is no longer located within the UL Standard. For information concerning the use and application of the requirements contained in this Standard, the current version of the UL Forewor
3、d is located on ULStandardsInfoNet at: COPYRIGHT 2007 UNDERWRITERS LABORATORIES INC.UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM UL2SUBJECT 1626AMAY 22, 2007No Text on This PageMAY 22, 2007SUBJECT 1626A3CONTENTSINTRODUCTION1 Scope . .42 Comp
4、onents . .43 Units of Measurement . .54 Undated References . .55 Fire Test . .55.1 General . .55.2 Test Arrangement . .65.3 Test method . .8UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM UL4SUBJECT 1626AMAY 22, 2007INTRODUCTION1 Scope1.1 These
5、 requirements cover the fire testing of residential sprinklers for use with smooth, flat, sloped ceilings having pitches not exceeding 8/12 for installation in accordance with the Standards for Installation of Sprinklers Sprinkler Systems in One-and Two-Family Dwellings and Manufactured Homes, NFPA
6、13D; Installation of Sprinkler Systems in Residential Occupancies up to and Including Four Stories in Height, NFPA 13R; and and Installation of Sprinklers, NFPA 13.1.1 effective May 22, 20091.2 Residential sprinklers covered herein are also required to comply with the fire and other applicable requi
7、rements in the Standard for Residential Sprinklers for Fire-Protection Service, UL 1626.1.2 effective May 22, 20091.3 The requirements contained herein are not intended to restrict the application of representative fire and other tests for special sprinklers, as referenced in NFPA 13, that are inten
8、ded to provide protection for specific fire hazards.1.3 effective May 22, 20091.4 These fire test methods and requirements contained herein are based upon the following installation conditions:a) A maximum distance from the floor to the ceiling peak of 24 ft (7.3 m).b) A maximum of two sprinklers ar
9、e installed within 3 ft (0.9 m). vertically of the peak.c) For sidewall sprinklers discharging across the slope, sprinklers are installed on one side of the room only.d) Installation is for smooth, flat ceilings only that do not extend into or serve as a ceiling for an upper level floor in the struc
10、ture.1.4 effective May 22, 20092 Components2.1 Except as indicated in 2.2, a component of a product covered by this Outline shall comply with the requirements for that component.2.1 effective May 22, 20092.2 A component is not required to comply with a specific requirement that:a) Involves a feature
11、 or characteristics not needed in the application of the component in the product covered by this Outline; orb) Is superseded by a requirement in this Outline.2.2 effective May 22, 2009UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM ULMAY 22, 2
12、007SUBJECT 1626A52.3 A component shall be used in accordance with its rating for the intended conditions of use.2.3 effective May 22, 20092.4 Specific components are accepted as being incomplete in construction features or restricted in performance capabilities. Such components are intended for use
13、only under limited conditions, such as temperatures not exceeding specified limits, and shall be used only under those specific conditions for which they have been investigated.2.4 effective May 22, 20093 Units of Measurement3.1 Values stated without parentheses are the requirement. Values in parent
14、heses are explanatory or approximate information.3.1 effective May 22, 20094 Undated References4.1 Any undated reference to a code or standard appearing in the requirements of this Outline shall be interpreted as referring to the latest edition of that code or standard.4.1 effective May 22, 20095 Fi
15、re Test5.1 General5.1.1 When fire tested as described in 5.1.2 5.3.5, a residential sprinkler shall limit temperatures as specified in 5.1.1 (a) (d) when tested at each rated spacing referenced in the installation instructions. Additionally, a maximum of two residential sprinklers shall operate with
16、in the test room and no sprinkler shall operate in the doorways. The sprinklers shall limit temperatures as followsa) The maximum temperature 3 inches (76 mm) below the ceiling at either location as illustrated in Figures 5.1, 5.4, 5.7, or 5.10 shall not exceed 600 F (316 C).b) The maximum temperatu
17、re 5-1/4 feet (1.6 m) above the floor shall not exceed 200 F (93 C).c) The temperature at the location described in (b) shall not exceed 130 F (54 C) for more than any continuous 2-minute period.d) The maximum ceiling material temperature 1/4 inch (6.4 mm) behind the finished ceiling surface shall n
18、ot exceed 500 F (260 C).See Figure 5.1 (pendent, upright, flush, recessed pendent, and concealed pendent sprinklers), or Figures5.4, 5.7, or 5.10 (sidewall sprinklers) for temperature measuring locations.5.1.1 effective May 22, 2009UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR D
19、ISTRIBUTION WITHOUT PERMISSION FROM UL6SUBJECT 1626AMAY 22, 20075.1.2 Residential sprinklers in each temperature rating are to be subjected to the tests specified in 5.2.1 5.3.5.5.1.2 effective May 22, 20095.2 Test Arrangement5.2.1 General5.2.1.1 Pendent, upright, flush, recessed pendent, and concea
20、led pendent sprinklers are to be subjected to both high and low corner fire test arrangements for the applicable rated spacings as illustrated in Figures 5.1 to 5.3. Sidewall sprinklers discharging across the slope are to be subjected to both high and low corner fire test arrangements for the applic
21、able rated spacings as described in Figures 5.4 to 5.6. Sidewall sprinklers discharging down the slope are to be subjected to both high and low corner fire test arrangements for the applicable rated spacings as described in either Figures 5.7 to 5.9, or 5.10 to 5.12.5.2.1.1 effective May 22, 20095.2
22、.2 Test room5.2.2.1 The test room dimensions for pendent, upright, flush, recessed pendent, and concealed pendent sprinklers are to be as specified in Figures 5.1 to 5.3. The test room dimensions for sidewall sprinklers discharging across the slope are to be as specified in Figures 5.4 to 5.6. The t