1、 ABB Group December 25, 2022 | Slide 1,DCS系统诊断S800 I/O部分,王永茂 ABB China Limited PAPIP, ABB Group December 25, 2022 | Slide 2,概述,S800 I/O是一种分布式和模块化的过程I/O系统,种类丰富,应用广泛。结合S800硬件特点、软件功能及实际经验,为工程师在现场能够快速、准确的发现故障并及时的进行处理提供通用的方法和思路。分析工具:硬件:模块LED灯软件:CBM、CBF diagnostics、DTM一般步骤典型案例S800 I/O模块更换步骤, ABB Group Dec
2、ember 25, 2022 | Slide 3,S800 I/O 故障诊断,硬件状态提示:LED软件状态提示:CBF、DTM故障排查步骤常见案例模块更换步骤, ABB Group December 25, 2022 | Slide 4,S800 I/O模块及LED灯, ABB Group December 25, 2022 | Slide 5,LED灯描述, ABB Group December 25, 2022 | Slide 6,LED与模块状态, ABB Group December 25, 2022 | Slide 7,S800 I/O 故障诊断,硬件状态提示:LED软件状态提示:C
3、BF、DTM故障排查步骤常见案例模块更换步骤, ABB Group December 25, 2022 | Slide 8,软件状态诊测:CBF, ABB Group December 25, 2022 | Slide 9,软件状态诊测:Control Builder M, ABB Group December 25, 2022 | Slide 10,软件状态诊测:DTM诊测, ABB Group December 25, 2022 | Slide 11,S800 I/O 故障诊断,硬件状态提示:LED软件状态提示:CBF、DTM故障排查步骤常见案例模块更换步骤, ABB Group Dece
4、mber 25, 2022 | Slide 12,故障处理:一般步骤,No,故障处理,LED,Tool,故障处理,Restart,Yes,Yes,No, ABB Group December 25, 2022 | Slide 13,S800 I/O 故障诊断,硬件状态提示:LED软件状态提示:CBF、DTM故障排查步骤常见案例模块更换步骤, ABB Group December 25, 2022 | Slide 14,常见故障:模块丢失,表明该模块的物理连接有问题,可能的原因如下:模块与底座是否完全扣合在一起,模块上的金属管脚是否有弯折的情况模块底座的机械锁是否完全锁定模块是否损坏,可换用一个
5、新的模块进行验证,硬件LED灯表现:故障灯为红灯其余指示灯全灭,CBF诊测信息:, ABB Group December 25, 2022 | Slide 15,常见故障: ModuleBus总线短路,I/O总线ModuleBus的电气接口在模块底座的左右两侧,用于连接相邻的IO模块,如果连接异常,如出现两针短路等情况,则会造成ModuleBus通信不正常,出现一个或多个模块无法识别。应该重新连接底座或更换相应底座。,硬件LED灯表现:一个或多个IO模块的故障灯为红灯其余指示灯全灭, ABB Group December 25, 2022 | Slide 16,常见故障:从站参数错误,表明I/