1、IEEE C37.234 Guide for Protective Relay Application to Power System Buses,B.Kasztenny (Chairman), S.Conrad (Vice-Chairman), P.Beaumont, K.Behrendt, O.Bolado, J.Boyle, G.Brunello, J.Burger, F.Calero, S.Chano, G.Dalke, A.Darlington, H.DoCarmo, D.Fontana, Z.Gajic, J.Holbach, L.Kojovic, F.Lopez, D.Lukac
2、h, D.McGinn, J.Miller, P.Mysore, J.OBrien, B.Pickett, S.Sambasivan, G.Sessler, V.Skendzic, J.Smith, D.Tholomier, M.Thompson, J.Uchiyama, D.Ware, D.Weers, R.Whittaker, R.Young, S.Zocholl,Presentation to the Main Committee of PSRC, January 14, 2010, Orlando, FL,迈鼎 http:/,Table of Contents,DefinitionsB
3、us configurationsIntroduction to bus protectionRelay input sourcesBus protection methodsApplication of bus protection schemesAnnexes,Definitions,23 new terms definedBus protection and primary equipment,breaker substitution Temporary usage of a bus tie breaker in a multiple bus configuration to subst
4、itute for one of the network elements circuit breakers, typically for the maintenance of the latter; also known as breaker transfer,check zone Nonselective part of a multi-zone bus protection system measuring current flows around the entire station and supervising selective tripping from individual
5、bus zones of protection,stub bus Area of a bus or line that becomes isolated from the original zone of protection or an area that loses protection due to the loss of sensing to zone protection relays,Bus design considerations,Continuity of service for the bus and essential network elementsEquipment
6、maintainability and network switching flexibilityEconomical and footprint constraintsSectionalizing requirements to avoid exceeding breaker fault dutiesEase of future bus expansion,Bus arrangements,Single busMain and transfer busDouble-bus double-breakerDouble-bus single-breakerBreaker-and-a-halfRin
7、g bus,Main and transfer bus,Main and transfer bus,Introduction to bus protection,Zones of protectionBus protection methodsScheme selection guidelines,Zones of protection,Dynamic zones of protection,Dynamic zones of protection,Dynamic zones of protection,Zones of protection,Bus protection methods,Dif
8、ferentialDifferentially-connected overcurrentInstantaneousTime-delayedPercentage-restrained differentialRestrainedAdvanced microprocessor basedHigh-impedance differentialResistor-stabilized overcurrentHigh-impedancePartial differential overcurrentFault bus,Bus protection methods,Zone-interlocked sch
9、emesSimple blockingDirectional blockingTime-coordinated relays overlapping the busProtection (sensors) built into the gas isolated switchgear*,* Not covered in the Guide,Scheme selection criteria,Bus arrangement and flexibilityFixed vs. switchable busesAvailability and characteristics of CTsFor reco
10、nfigurable buses, availability of auxiliary contacts of disconnect switchesPerformance requirementsSecurity, Selectivity, Speed, SensitivityCost and complexity,Scheme selection,Relay input sources,Current transformersTypesAccuracy classesEquivalent circuit & time to saturationNo universal CT require