山东建筑大学《建筑电气安装技术》课后题答案.doc
作业19解冷加工设备属长期负荷,Pe=(10×3)+(4×8)+(1.5×10)+(2.8×11)=107.8KW查表2-2,大批量生产冷加工设备Kx=0.18,cos=0.5,tg=1.73,Pc=Kx×Pe=19.4KW,Qc=Pc×tg=33.61KVar,Sc=(Pc2+Qc2)1/2=38.81KVAIc=Sc/(1.73×0.38)=58.96A10解1)冷加工机床属长期负荷,Pe1=(7.5×4)+(4×6)=54.0KW查表2-2,大批量生产冷加工设备Kx1=0.18,cos1=0.5,tg1=1.73,Pc1=Kx1×Pe1=9.72KW,Qc1=Pc1×tg1=16.84KVar,Sc1=(Pc12+Qc12)1/2=19.44KVAIc1=Sc1/(1.73×0.38)=29.54A2)生产用通风机属长期负荷,Pe2=(4.5×3)=13.5KW查表2-2,生产用通风机Kx2=0.8,cos2=0.8,tg2=0.75,Pc2=Kx2×Pe2=10.8KW,Qc2=Pc2×tg2=8.1KVar,Sc2=(Pc22+Qc22)1/2=13.5KVAIc2=Sc2/(1.73×0.38)=20.54A3)生产用水泵属长期负荷,Pe3=(2.8×2)=5.6KW查表2-2,生产用水泵Kx3=0.8,cos3=0.8,tg3=0.75,Pc3=Kx3×Pe3=4.48KW,Qc3=Pc3×tg3=3.36KVar,Sc3=(Pc32+Qc32)1/2=5.6KVAIc3=Sc3/(1.73×0.38)=8.52A4)同期系数Kp=0.9,Kq=0.95,Pc=Kp(Pc1+Pc2+Pc3)=0.9×25=22.5KWQc=Kq(Qc1+Qc2+Qc3)=0.95×25=28.3KvarSc=(Pc2+Qc2)1/2=36.15KVAIc=Sc/(1.73×0.38)=55.0A冷加工机床组Pc1=9.72KWQc1=16.84KVarSc1=19.44KVAIc1=29.54A通风机组Pc2=10.8KWQc2=8.1KVarSc2=13.5KVAIc2=20.54A水泵组Pc3=4.48KWQc3=3.36KVarSc3=5.6KVAIc3=8.52A母线总负荷Pc=22.5KWQc=28.3KvarSc=36.15KVAIc=55.0A14解120户平均分配在3相供电线路,每相供电线路为40户;每户4KW,A相供电线路PeA=40×4=160KW查表2-6,Kx=0.45,cos=0.9,tg=0.48,每相供电线路PcA=PeA×Kx=72KWQcA=PcA×tg=34.56KvarScA=(PcA2+QcA2)1/2=79.86KVAIcA=ScA/(0.22)=363.02A三相供电线路总计算负荷Pc=PcA×3=216KWQc=QcA×3=103.68KvarSc=(Pc2+Qc2)1/2=239.59KVAIc=Sc/(1.732×0.38)=363.02A15解第1单元PeA1=3×2×6=36KWPeB1=2×2×6=24KWPeC1=2×2×6=24KW第2单元PeA2=2×2×6=24KWPeB2=3×2×6=36KWPeC2=2×2×6=24KW住宅各相总负荷PeA=PeA1+PeA2=36+24=60KWPeB=PeB1+PeB2=24+36=60KWPeC=PeC1+PeC2=24+24=48KW最大相与最小相之差P=60-48=12KW住宅三相总负荷Pe=PeA+PeB+PeC=60+60+48=168KWP/Pe=12/168=7.14%<10%按三相对称负荷计算,三相总负荷为168KW。查表2-6,Kx=0.65,cos=0.9,tg=0.48,三相总计算负荷为Pc=Pe×Kx=109.2KWQc=Pc×tg=54.42KvarSc=(Pc2+Qc2)1/2=121.13KVAIc=Sc/(1.73×0.38)=184.25A作业二P104题12部分解1 消防电梯Sc=120/0.7=171.43kVA, Ic=171.43/(1.732*0.38)=260.46A。4根导线穿塑料管敷设,室内温度取25,按发热条件3根相线每相选150mm2,零线选75mm2。自动空气断路器Izd1Ic=260.46A,Izd31.2(Iq.M(max)+Ic(n-1)=1.2(6*32.56+227.9)=507.92A,选额定电压400V、TIME1N400型断路器,Izd1取315A,Izd3整定为508A;因未给出短路电流,通断电流不选。2 防排烟风机Sc=150/0.8=187.5kVA, Ic=187.5/(1.732*0.38)=284.89A。4根导线穿塑料管敷设,室内温度取25,按发热条件3根相线每相选70mm2*2并联,零线选70mm2。自动空气断路器Izd1Ic=284.89A,Izd31.2(Iq.M(max)+Ic(n-1)=1.2(6*32.56+252.3)=537.23A,选额定电压400V、TIME1N400型断路器,Izd1取315A,Izd3整定为537.23A;因未给出短路电流,通断电流不选。3 以下计算与上述类似。4 消防总负荷Sc=475.55kVA,Ic=475.55/(1.732*0.38)=722.54A。4根导线穿塑料管敷设,室内温度取25,按发热条件3根相线每相选120mm2*4并联,零线选120mm2*2并联。自动空气断路器Izd1Iz=908A,Izd21.2(1.35Iq.M(max)+Ic)=1.2(6*37/(0.8*1.732*0.38)+722.54)=1.2(421.63+722.54)=1373A,Izd31.1(1.8*1.35*Iq.M(max)+Ic)=1.1(1.8*421.63+722.54)=1.1(758.93+722.54)=1629.62A,选额定电压400V、TIME1N800型断路器,Izd1取800A,Izd2整定为1373A,Izd3整定为1629.6A;因未给出短路电流,通断电流不选。作业三 一单位容量法P156 应用实例5 填写原始数据单光源为36W双管荧光灯,室长I=19.2m,宽b=12.8m,高h=1.9m,顶棚反射比c=0.7,墙壁反射比t=0.5,地面反射比f=0.1,桌面平均照度Eav=300lx。6 计算室空间比RCR=1.27 确定灯具单位容量按RCR=1.2,以及半直接配光的荧光灯,从表6-16中查得P0=0.03838 总面积容量P= P0·A·Eav=0.0383·(19.2·12.8)·300=2323.8W5.灯具安装数量N=2323.8/72=39.240套二利用系数法P158 应用实例1填写原始数据单光源为40W单管荧光灯,室长I=9m,宽b=6m,高h=3m,顶棚反射比c=0.7,墙壁反射比t=0.5,地面反射比f=0.2,地面平均照度Eav=100lx。2 计算室空间比RCR=4.167,RI=1.23 灯具维护系数k=0.84 确定利用系数查单管荧光灯利用系数表,得U=0.7,=2200lm;5. 灯具安装数量N=Eav·A/(·U·k)=100·36/(2200·0.7·0.8)3套